Products
MEsoftstart


Model |
D02 |
D03 |
I00 |
I01 |
I02 |
I03 |
I04 | |
---|---|---|---|---|---|---|---|---|
Nominal / max current |
A |
16 / 50 |
32 / 100 |
100 / 240 |
200/480 |
390 / 730 |
600 / 1440 |
900 / 1600 |
Phases controlled |
- |
Two |
Three | |||||
Operating interface |
- |
none |
Potentio-meter |
Potentio-meter / TFT |
TFT | |||
Supply voltage |
Vac |
400 |
400 | 525 | 690 | |||||
Output power range at 400V: | ||||||||
3-wire |
kW |
3 - 10 |
6 - 20 |
11 - 55 |
22 - 132 |
37 - 200 |
75 - 315 |
110 - 560 |
6-wire |
kW |
n/a |
10 - 32 |
18.5 - 90 |
37 - 160 |
55 - 355 |
110 - 560 |
132 - 800 |
Output power range at 525V: |
||||||||
3-wire |
kW |
n/a |
n/a |
15 - 73 |
30 - 132 |
45 - 250 |
90 - 450 |
110 - 630 |
6-wire |
kW |
n/a |
n/a |
22 - 110 |
45 - 250 |
75 - 450 |
160 - 710 |
200 - 1000 |
Output power range at 690V: | ||||||||
3-wire |
kW |
n/a |
n/a |
18.5 - 90 |
37 - 300 |
55 - 355 |
110 - 630 |
132 - 800 |
6-wire |
kW |
n/a |
n/a |
30 - 160 |
75 - 315 |
110 - 630 |
200 - 900 |
250 - 1400 |
Operating temperature |
°C |
-10 to +60 (derating above 50°c) | ||||||
Operating altitude |
m(amsl) |
3000 (derating above 1400m) |
Model |
D02 |
D03 |
I00 |
I01 |
I02 |
I03 |
I04 | |
---|---|---|---|---|---|---|---|---|
Nominal / max current |
A |
16 / 50 |
32 / 100 |
100 / 240 |
200/480 |
390 / 730 |
600 / 1440 |
900 / 1600 |
Phases controlled |
- |
Two |
Three |
Three |
Three |
Three |
Three |
Three |
Operating interface |
- |
none |
none |
Potentio-meter |
Potentio-meter / TFT |
TFT |
TFT |
TFT |
Supply voltage |
Vac |
400 |
400 |
400 | 525 | 690 |
400 | 525 | 690 |
400 | 525 | 690 |
400 | 525 | 690 |
400 | 525 | 690 |
Output power range at 400V: | ||||||||
3-wire |
kW |
3 - 10 |
6 - 20 |
11 - 55 |
22 - 132 |
37 - 200 |
75 - 315 |
110 - 560 |
6-wire |
kW |
n/a |
10 - 32 |
18.5 - 90 |
37 - 160 |
55 - 355 |
110 - 560 |
132 - 800 |
Output power range at 525V: |
||||||||
3-wire |
kW |
n/a |
n/a |
15 - 73 |
30 - 132 |
45 - 250 |
90 - 450 |
110 - 630 |
6-wire |
kW |
n/a |
n/a |
22 - 110 |
45 - 250 |
75 - 450 |
160 - 710 |
200 - 1000 |
Output power range at 690V: | ||||||||
3-wire |
kW |
n/a |
n/a |
18.5 - 90 |
37 - 300 |
55 - 355 |
110 - 630 |
132 - 800 |
6-wire |
kW |
n/a |
n/a |
30 - 160 |
75 - 315 |
110 - 630 |
200 - 900 |
250 - 1400 |
Operating temperature |
°C |
-10 to +60 (derating above 50°c) |
-10 to +60 (derating above 50°c) |
-10 to +60 (derating above 50°c) |
-10 to +60 (derating above 50°c) |
-10 to +60 (derating above 50°c) |
-10 to +60 (derating above 50°c) |
-10 to +60 (derating above 50°c) |
Operating altitude |
m(amsl) |
3000 (derating above 1400m) |
3000 (derating above 1400m) |
3000 (derating above 1400m) |
3000 (derating above 1400m) |
3000 (derating above 1400m) |
3000 (derating above 1400m) |
3000 (derating above 1400m) |